SIMH-FR FE 180
HIGH TEMPERATURE, RESISTANT TO FIRE SILICONE CABLES
These cables fields of use as a control and power supply cable they are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power for a period of 180 minutes under the existing fire conditions (at a temperature of 750OC and under the flames ). Also these cables shall satify EN50200 test which is a fire resistant with mechancal shock test (under the conditions at 842oC and mechenical shock) by the classes PH15-PH30-PH60-PH90, if it has requsted, Because of their unique features, they can be used; on the fire alarm systems, on the equipment and devices which are connected to the fire alarm devices, in the environments which have no corrosive gases are emitted in the event of fire. These cables are used at schools, airpots, hospitals, etc.
Conductor: IEC 60228 Class 5, TS/DIN EN 60228 Class 5, Flexible copper wires, plain;
Insulation: Speacial silicone rubber compound
Core identification: According to TS HD 308 S2 & VDE 0293-308, Acc. to TS/DIN EN 50334 black cores with, white numerals with green/yellow after 5 cores
Lay-up: Cores laid up in layers of optimum pitch
Outer sheath: Silicone rubber compound
Sheath colour: RAL 2009, Orange
Standard: VDE 0250, DIN VDE 0282-15 and, TS HD 22.15 S1, (Designed according to)
Insulation resistance: Min. 20 MΩ.km
Temp. at conductor: + 180 oC
Short circuit tempetarure: +200oC
Rated voltage: 300 / 500V ; 450/750 V ≥4,0 mm2
Test voltage: 2000 V ; 2500 V ≥4,0 mm2
Temperature range: Fixed: - 60 oC ~ + 180 oC, Mobile: - 25 oC ~ + 180 oC
Min. bending radius: Fixed: 4 x D, Mobile: 7,5 x D
Flame retardance test: IEC 60332-1 & EN 50265-2-1, IEC 60332-3 & EN 50266-2-4
Fire resistant with mechanical shock*Upon request: DIN EN 50200 ; PH 15 (15 minutes), DIN EN 50200 ; PH 30 (30 minutes), DIN EN 50200 ; PH 60 (60 minutes), DIN EN 50200 ; PH 90 (90 minutes)
Insulation integrity: IEC 60331 , VDE 0472-814